Wherever the process pressure has to be indicated locally and, at the same time, circuits need to be switched, the model PGS21.1x0 switchGAUGE finds its use.
Switch contacts (electrical alarm contacts) make or break circuits dependent upon the pointer position of the indicating measuring instrument. The switch contacts are adjustable over the full extent of the scale range (see DIN 16085), and are mounted predominantly below the dial, though also partly on top of the dial. The instrument pointer (actual value pointer) moves freely across the entire scale range, independent of the setting.
The set pointer can be adjusted using a removable adjust ment key in the window.
Switch contacts consisting of several contacts can also be set to a single set point. Contact actuation is mad when the actual value pointer travels beyond or below the desired set point.
The pressure gauge is manufactured in accordance with DIN 16085 and fulfils all requirements of the relevant standards (EN 837-1) and regulations for the on-site display of the working pressure of pressure vessels.
As switch contacts, magnetic snap-action contacts, reed switches and delectronic contacts are available. For triggering programmable login controllers (PLC), electronic contacts and reed switches can be used.
Specifications
Nominal size in mm: 100、160
Accuracy class: 1.0
Scale ranges: 0 ... 0.6 bar [0 ... 8.7 psi] to 0 ... 600 bar [0 ... 8,702.26 psi] other units(e.g, psi,kPa) available or all other equivalent vacuum or combined pressure and vacuum ranges
Scale: Single scale、 Dual scale
Pressure limitation
Steady: Full scale value
Fluctuating: 0.9 x full scale value
Short time: 1.3 x full scale value
Connection location: Lower mount (radial), Lower back mount
process connection (copper alloy): G☒B、☒NPT、M20x1.5, others on request
Permissible temperature
Medium: +80°C [+176°F], Higher medium temperature on request
Ambient: -20 ... +60°C [-4 ... +140°F]
Temperature effect: When the temperature of the measuring system deviates from the reference temperature (+20°C), max. ±0.4%/10K of full scale value
Case: Stainless steel
Case filling: Without
Wetted materials
Process connection, pressure element
<100 bar: Copper alloy, trumpet form
≥ 100 bar: Stainless steel 316L, helical type
Non-wetted materials
Case, bayonet ring: Stainless steel
Movement: Copper alloy, wear parts argentan
Dial: Aluminium, white, black lettering
Instrument pointer: Aluminium, black
Set pointer: Aluminium, red
Window: Polycarbonate、Laminated safety glass
Ingress protection per JB/TP273-1999: IP54
Electrical connection: Cable socket PA 6, BLACK, pER vde 0110 insulation group C/250V, Cable gland M20 x 1.5, Strain relief, 6 screw terminals + PE for conductor cross-section 2.5 mm
Switching function
The switching function of the switch is indicated by index 1, 2 or 3
Model 8XX.1: Normally open (clockwise pointer motion)
Model 8XX.2: Normally closed(clockwise pointer motion)
Model 821.3 and 851.3: Change-ove; one contact breaks and one contact makes simultaneously when pointer reaches set point
For further information on switch contacts, see data sheet AC 08.01
Other versions
Contact model 821 with separate circuits
Contact model 821 as change-over contact (break or make simultaneously at the set point)
Contact model 821 width cable break monitoring (parallel resistance 47kΩ and 100kΩ)
Contact materials for contact model 821: Platinum-iridium alloy and gold-silver alloy
Contacts fixed, without contact adjustment lock
Contact adjustment lock leaded
Contact adjustment key fixed
Connerctor (instead of cable socket)
Accessories
Panel mounting flange, polished stainless steel
Surface mounting flange, stainless steel
Surface mounting lugs on the back, stainless steel
Sealings (models IV20/IV21, see data sheet AC 09.19, and models IV10/IV11, see data sheet AC 09.22)
Syphons (model 910.15, see data sheet AC 09.06)
Overpressure protector model 910.13, see data sheet AC 09.04)
Cooling element (model 910.32, see data sheet AC 09.21)
Diaphragm seals
Ordering information: Model / Nominal size / Type of contact and switching function / Scale range / Process connection / Connection location / Options